The room map of the apartment provides the residents of the apartment with the necessary information about the used colours and shades, interior finishing materials, coatings, lighting, switches, sockets, and plumbing equipment. In addition, it gives information about the apartment’s exterior and interior doors, thresholds, skirting boards and windows.
Replace the ventilation unit filters in accordance with the ventilation unit’s operating and maintenance instructions.
Do not switch off the ventilation unit completely (only allowed for maintenance work). Check the cleanliness of the filters.
Also, clean the intake and exhaust vents and grilles regularly as required. They must not be clogged. NB! The position of the centre of the vent must not be changed.
First, make sure that the device/connector is securely fastened. If it still leaks, unscrew the device, clean it and install a new seal.
If it is not possible to stop the leaking yourself, notify the building’s manager immediately.
Open the trap lid and clean it.
If it is not possible to eliminate the clogging yourself, notify the building manager immediately.
In the event of a water main break, the ball valves at the water meters must be closed. The valves can be accessed through a service hatch. The valves are located behind the suspended ceiling in the hallway, in the sanitary unit or kitchen – check the exact location in the as-built drawing.
Check if the main circuit breaker of the apartment is switched off. If the circuit breaker is switched off and turns off again when switched on, check the electrical equipment and contact the management company.
Check the circuit breaker and the residual current device.
Make sure that the heating circuit breaker is turned on in the switchboard. If the problem persists, contact the building’s administrator.
When the set air temperature in the room is reached, the underfloor heating switches off automatically and the floor may not be evenly warm.
The shut-off valves of the apartment heating system are located in the collector cabinet. In the event of a leak, close the shut-off valve and contact the building’s manager immediately.
Notify the administrator immediately, who can lock it.
The lock case must be lubricated with lock oil at least twice a year. This should be done more often in case of frequent use. If that doesn’t work, adjust the lock bar or latch and contact the administrator.
The moving parts of the handle and knob must be lubricated with lock oil or grease at least once a year. If that doesn’t work, adjust the lock bar or latch and contact the administrator
Do not use force when opening and closing the door/window. If it is difficult to open and close the door/window, their position in relation to the frame must be adjusted. Difficulty closing or opening them may be caused by movement of the building’s structures, expansion due to moisture or loosening of lock/hinge attachments.
Check that the terrace’s shower trap/drain under the terrace is clean. Clean the sludge that has accumulated in the trap.
It is recommended to replace the ceramic tiles in the bathroom only by tiling over old ones, as there is a risk of damaging the waterproofing when removing the tiles.
Care must be taken to ensure that the surface temperature of the parquet floor does not exceed 26°C in the case of underfloor heating. Compared to central or stove heating, cracks are more common when it comes to underfloor heating.
Differences in colour tones (for example, at the edges of carpets) will level off over time if the covered area is exposed to daylight.
Clean the sauna bench with a brush and warm water, which includes a mild detergent.
Appropriate adhesives, dowels or other means must be used to secure items to the wall or ceiling.
If possible, avoid securing objects to the room floor. Underfloor heating pipes are installed throughout the whole apartment.
If the apartment has a floating parquet, it must be able to swell or shrink (i.e. move freely in the plane of the floor covering) depending on the humidity. Drilling holes and installing fasteners would reduce this possibility and create the risk of the floor covering rising or cracking.
Be extremely careful when drilling a hole in plaster walls, as most supply networks are inside plaster walls. Avoid drilling holes closer than 0.5 m to supply networks.
It is strictly forbidden to drill holes in the load-bearing or slab walls (milling and cutting holes).
It is not recommended to drill holes in the tiled floor of the bathroom, as this may damage the underfloor hydro-insulation and the heating pipes.
It is recommended to use moisture-resistant adhesives, silicone paste or tape fasteners. Avoid drilling holes into areas where water may get in. Do not drill holes in the wall between the bathroom and the hallway.
If there is notch, it should be repaired so that moisture does not damage the countertop more.
In the event of an accident, notify the administrator or the emergency services of the management company immediately during non-working hours.
Follow the instructions for sending warranty notices on Live’s portal. Also, inform about this defect by e-mail, the address of which you can find on the portal. You will be contacted and an action plan will be agreed upon. The builder undertakes to eliminate the defects in accordance with the agreed action plan.
Follow the instructions for sending warranty notices on Live’s portal. Also, inform about this defect by e-mail, the address of which you can find on the portal. You will be contacted and an action plan will be agreed upon. The builder undertakes to eliminate the defects in accordance with the agreed action plan.